• Travel: Linear Motion: 3 - 100 mm Rotary Motion: 30° - 120° Rotation Angle
  • Input and Communication Protocol: HART, Two-Wire controlled (FY301) Fieldbus (FY302)
  • Power Supply: 4 mA to 20 mA Input via controller.
  • Indicator: Rotative LCD, with 4-1/2 numerical digit and 5-Character alphanumerical.
  • Gauge: 0 to 160 psi scale, Acrylic display, 304 Stainless Steel connection and flexible parts in Brass.
  • Hazardous Area Certifications: Explosion proof, weather proof, dust ignition proof, intrinsically safe, non-incendive according to the NEC500, CEC, CENELEC, IEC standards.
  • Flow Characterization: Linear, Equal Percentage, Quick Opening, 16-pint freely configurable table.
  • Temperature Limits:
    • Operation: -40°C to +85°C (-40°F to +185°F)
    • Storage: -40°C to +90°C (-40°F to +194°F)
    • Display: -10°C to +75°C (+14°F to +167°F)
    • Display: -40°C to +85°C (-40°F to +185°F) without damage
    • Remote Sensor: -40°C to +105°C (-40°F to +221°F)
  • Voltage Drop: 11 Vdc Max / 20 mA (equivalent to 550Ω)
  • Humidity Limits: 0 - 100% RH (Relative Humidity non-condensable)
  • Current: 3.8 mA (minimum)
  • Position Sensor: Non-Contact Hall Effect Sensor
  • Pressure Supply: 1.4 - 7 bar (20-100 psi) ANSI/ISA S7.0.01-1996
  • Resolution / Repeatability: < 0.1% F.S.
  • Ambient: 0.8%/20°C of span.
  • Electrical Connection:
    • 1/2"-14 NPT
    • 3/4"-14 NPT (with 316 Stainless Steel adapter for 1/2"-14 NPT)
    • 3/4"-14 BSP (with 316 Stainless Steel adapter for 1/2"-14 NPT)
    • 1/2"-14 BSP (with 316 Stainless Steel adapter for 1/2"-14 NPT)
  • Pneumatic Connections: Supply and output: 1/4"-18 NPT, Gauge: 1/8"-27 NPT
  • Material of Construction:
    • Injected low copper aluminum with polyester painting or 316 Stainless Steel housing, with Buna N O-Rings on cover (NEMA 4X, IPW 66).
read more...
FY301-00-0DA-I3
FY301-00-0DA-I3
$1,128.00
  • FY301= Smart Valve  Positioner  HART & 4-20mA
  • 0=No Indicator/Display
  • 0=Without Bracket
  • 0=1/2" 14 FNPT Electrical Connection
  • D=No Magnet - Double Acting
  • A=With 3 Stainless Steel Gauges
  • I3= CSA

FY301-10-0Z0/R1
FY301-10-0Z0/R1
$765.00 While Supplies Last
FY302-00-0Z0-I3
FY302-00-0Z0-I3
$1,246.30 $1,133.00 9% off While Supplies Last

Agency Approvals

  • CEPEL
  • CSA
  • EXAM
  • FM
  • NEMKO ATEX

Environmental Protection

  • Dust Ignition-Proof
  • Explosion-Proof
  • Intrinsically Safe
  • Non-Incendive
  • Weatherproof

Supply Pressure

  • 1.4 to 7 bar (20 to 100 psi, 140 to 700 kPa) Free of oil, dust and water, as pwer ANSI/ISA S7.0.01-1996

Operating Temperature - Display

  • -10° to 75° C (14° to 167° F)
  • -40° to 85° C (-40° to 185° F), Without Damage

Storage Temperature

  • -40° to 90° C (-40° to 194° F)

Humidity

  • 0 to 100% Relative Humidity

Process Temperature

  • Operation: -40° to 85° C (-40° to 185° F)

Consumption

  • 0.35 Nm³/h (0.20 SCFM) at 1.4 bar (20 psi, 140 kPa) Supply.
  • 1.10 Nm³/h (0.65 SCFM) at 5.6 bar (80 psi, 560 kPa) Supply.

Repeatability

  • <0.1% Full Scale

Resolution

  • <0.1% of Full Scale

Vibration Effect

  • ±0.3% /g of span during the following conditions: 5 to 15 Hz at 4 mm constant displacement; 15 to 150 Hz at 2g; 150-2000 Hz at 1g
  • Comply with the IEC60770-1 standard.

Electromagnetic Interference Effect

  • According to the IEC 61326:2002 standard

Actuator Type

  • Double Acting
  • Linear
  • Rotary
  • Single Action

Input Power

  • Bus powered: 9 to 32 Vdc. Current consumption quiescent 12 mA.
  • HART 4 mA to 20 mA Input via Controller. Voltage Drop equivalent to 550 Ohms. Input protected against reverse polarity & transient suppressor.

Electrical Connectors

  • 1/2" NPT

Voltage Drop

  • 11 Vdc maximum / 20 mA (equivalent to 550 Ohms)

Display

  • 4-1/2-Digit LCD Indicator

Configuration

  • HART: By Digital Communication using the Configuration softwares CONF401, DDCON 100, FDT/DTM, AssetView or HPC401. Also Configurable using third-party Configuration tools, & can be partially configured through local Adjustment using the Smar magenetic tool.

Gauge

  • For Pressure monitoring and Output Supply. 0 to 160 psi scale. Acrylic display, 304 Stainless Steel connections & flexible parts in Brass.

Current

  • HART: 3.8 mA (minimum)

Enclosure/Body Material

  • 316 Stainless Steel
  • Injected Low Copper Aluminum

Enclosure Finish

  • Polyester (Gray Munsell N 6.5) Paint

O-Ring Material

  • Buna-N