Images are representations only.

Vegator 141 Signal Conditioning

Brand: VEGA
The VEGATOR 141 is a signal conditioning instrument for level detection for sensors with Analog measured data transmission such as typically capacitive electrodes, hydrostatic pressure transmitters or process pressure transmitters.

Simple monitoring and control functions can be realized.

Typical applications are pump control (On/Off) and monitoring functions such as overfill and dry run protection.
Features
  • Compact Separator with Alarm Function for Limit Level
  • Comprehensive Monitoring Detects Short circuit and Measuring Line Break as Well as Malfunctions In the Sensor
  • Simple Mounting Through Carrier Rail as Well as Detachable, Coded Terminals
show more
The VEGATOR 141 is a signal conditioning instrument for level detection for sensors with Analog measured data transmission such as typically capacitive electrodes, hydrostatic pressure transmitters or process pressure transmitters.

Simple monitoring and control functions can be realized.

Typical applications are pump control (On/Off) and monitoring functions such as overfill and dry run protection.
Features
  • Compact Separator with Alarm Function for Limit Level
  • Comprehensive Monitoring Detects Short circuit and Measuring Line Break as Well as Malfunctions In the Sensor
  • Simple Mounting Through Carrier Rail as Well as Detachable, Coded Terminals

Specifications

Brand

Ambient Temperature Range

  • -20° to 60° C (-4° to 140° F)

Approvals & Certifications

  • ATEX
  • GOST
  • IEC
  • SIL 2

Consumption

  • 2 W (8 VA)

Display

  • LED Display

Electrical Connectors

  • 0.25 mm² (AWG 23) to 2.5 mm² (AWG 12) - Wire Cross Section
  • EN 50022 / 60715
  • Screw Terminal

Environmental Protection

  • IP20

Hysteresis

  • 100 µA - Switching Threshold Hysteresis

Operating Voltages

  • 24-230 Vac
  • 24-65 Vdc
  • 50/60 Hz

Relay Output

  • Breaking Capacity: 50 mW Min., 500 VA, 54 W DC, Max.
  • Quantity 1 x Operating Relay, 1 x Fail-safe Relay - Optional
  • Switching Current: 10 µA Min., 3 A AC, 1 A DC, Max.
  • Switching Voltage: 10 mVdc Min., 250 Vac, 60 Vdc, Max.
  • Switch-On/Switch-Off Delay - 2/6/8 seconds, ± 20 % - Adjustable Delay
  • Switch-On / Switch-Off Delay: 150 milliseconds, ± 10 % - Basic Delay

Sensor Input

  • Active Input: Sensor Supply through VEGATOR 141
  • Current Limitation: through Internal Resistance 23 mA(100 ohms, ± 1 %) - Passive Input
  • Current Limitation: through Internal Resistance 23 mA(200 ohms, ± 1 %) - Active Input
  • Detection: ≤ 3.6 mA (Line Break), ≥ 21 mA (Short Circuit)
  • Number of Sensors: 1 x 4-20 mA
  • Passive Input: Sensor Has an Own Power Supply

Switch Type

  • SPDT Contact - Floating

Terminal Voltage

  • 18.2 Vdc, ± 5 % - Idle State

Transmission Value

  • 4-20 mA - Analog Sensors