Images are representations only.

T82 Programmable HART® Temperature Transmitter

Brand: Pyromation
The T82 programmable HART® field temperature transmitter is a 2-wire unit with analog output. It includes input for RTDs: resistance inputs in 2-wire, 3-wire, and 4-wire connections; thermocouples and voltage signals.

The transmitter can be supplied with or without a digital display, in a general-purpose aluminum screw-cover housing.

The T82 can be programmed using a HART® protocol handheld terminal. When supplied with a digital display, the LCD display shows the current measured value.

When specified, the T82 transmitter is available with an optional Safety Integrity Level Rating (SIL) for critical applications.
Features
  • Universally programmable with HART® protocol for various input signals
  • 2-wire, single, analog output (4 to 20) mA
  • Undervoltage detection
  • Highly accurate in entire operating temperature range
  • Approvals: FM and CSA (IS, NI)
  • Galvanic isolation
  • Output simulation
  • Customized measuring range setup or expanded setup
show more
The T82 programmable HART® field temperature transmitter is a 2-wire unit with analog output. It includes input for RTDs: resistance inputs in 2-wire, 3-wire, and 4-wire connections; thermocouples and voltage signals.

The transmitter can be supplied with or without a digital display, in a general-purpose aluminum screw-cover housing.

The T82 can be programmed using a HART® protocol handheld terminal. When supplied with a digital display, the LCD display shows the current measured value.

When specified, the T82 transmitter is available with an optional Safety Integrity Level Rating (SIL) for critical applications.
Features
  • Universally programmable with HART® protocol for various input signals
  • 2-wire, single, analog output (4 to 20) mA
  • Undervoltage detection
  • Highly accurate in entire operating temperature range
  • Approvals: FM and CSA (IS, NI)
  • Galvanic isolation
  • Output simulation
  • Customized measuring range setup or expanded setup
1 model matching criteria
PYROMATION XP Temp Xmtr, 4-20mA HART, Dsp,Config CH1:RTD-3W, CH2:Inactv, 100ohmPLT,Upscale,0-100°C show more
Transmitter
  • T76T82-D10: (4-20mA) Dual Input, HART (4-20mA) Temperature Transmitter
    • cw Digital Display, Glass Lid
    • Explosion Proof Aluminum Housing
    • FM/CSA, XP, DIP Class I Div I and Div II, Groups A,B,C,D
  • Field Transmitter with digital display and explosion-proof aluminum housing
  • 3I: Ch1: RTD 3-Wire. Ch2: Inactive
  • 85: Sensor Input Channel 1: 100 Ohm Platinum (α = 0.003 85 °Cˉ¹)
  • 00: No Second Channel
  • A: Ch 1 = Process Variable, Ch 2 = inactive
  • U: Upscale burnout
  • S: (0-100) Configured Temp Range: ( 0 to 100° )
  • C: Celsius (on Display)
1 In Stock
$813.82USD

Specifications

Brand

Output Signal

  • Analog 4-20 mA or 20-4 mA

Transmission as

  • Temperature Linear
  • Resistance Linear
  • Voltage Linear

Minimum Current Required

  • 3.5 mA
  • Multidrop Mode - 4 mA

Current Limit

  • ≤ 23 mA

Response Time

  • Resistance Thermometer (RTD) - 0.9 to 1.3 s (Depends on The Connection Method 2/3/4 - Wire)
  • Thermocouples (TC) - 0.8 s
  • Reference Temperature - 0.9 s

Failure

  • ≤ 3.6 mA or ≥ 21 mA

Electric Connection

  • 3/4” NPT Conduit Connection x 1/2” NPT Process Connection

Certifications & Approvals

  • CSA
  • FM
  • CE
  • SIL