User Configurable from 0 to 32 Seconds (via Digital Communication).
Overpressure & Static Pressure Limits
psi: 2,000 (bar: 137.9, MPa: 14) for Ranges 2, 3, and 4
psi: 4,500 (bar: 310.3, MPa: 31) for Range 5
Operating Temperature - Display
-20° to 80° C (-4° to 176° F)
-40° to 85° C (-40° to 185° F), Without Damage
Storage Temperature
-40° to 100° C (-40° to 212° F)
Temperature Effect
±[0.02% URL +0.06% of Span], per 20° C (68° F) for Span >=0.2 URL | ±[0.023% URL +0.045% of Span], per 20° C (68° F) for Span <0.2 URL
Ambient Temperature
-40° to 85° C (-40° to 185° F)
Humidity
0 to 100% Relative Humidity
Process Temperature
-40° to 100° C (-40° to 212° F)
Accuracy
For Ranges 2, 3, 4, or 5: ±0.075% of Span (for Span >=0.1 URL) ±[0.0375 + 0.00375 URL/SPAN % of Span (for Span < 0.1 URL)
Stability
±0.15% of URL for 5 years
Volumetric Displacement
>0.15 cm³ (0.01 in³)
Electromagnetic Interference Effect
Approved according to IEC61326-1:2006, IEC61326-2-3:2006, IEC61000-6-4:2006, IEC61000-6-2:2005
Media
Gas
Liquids and Gases
Steam
Power Supply Effect
±0.005% of Calibrated Span Per Volt
Input Power
Bus powered: 9 to 32 Vdc. Current consumption quiescent 12 mA.
Output Impedance: Intrinsic Safety (assuming an IS barrier in the power Supply) from 7.8 kHz to 39 kHz should be greater or equal to 400 Ohms.
Output Impedance: Non-intrinsic Safety from 7.8 kHz to 39 kHz should be greater or equal to 3,000 Ohms.
Electrical Connectors
1/2" NPT
Output
4-20 mA
Digital Only
Turn-On Time
Foundation fieldbus: approximately 10 Seconds
Display
4-1/2-Digit LCD Indicator
Configuration
Foundation Fieldbus: Basic configuration may be done using local Adjustment magnetic tool if device is fitted with display. Complete configuration is possible using remote, SYSCON (LD292), Smar ProfibusView & Simatic PDM.