• Operating Range: 
    • 1.25 - 50 ft (0.4 - 15.2 m)
  • Accuracy: ±0.25% of Detected Range
  • Programming: Interface with RST-3001 Programmer, User Selected Units
  • Output:
    •  4-20mA
    • 4-20mA with (2) NPN Trip Points
  • Electrical Connection:
    • 4 or 5 Conductor Shielded Cable or 5-Pin Micro Connector
    • 12 - 28 VDC
  • Temperature Range:
    • -40°F to +140°F (-40°C to +60°C)
  • Materials of Construction:
    • Housing: PC/PET Upper Housing
  • CSA Class 1, Div. 2, Groups A, B, C, D
  • IP65
The above description encapsulates the entire product series. Specifications for individual configurations may vary depending on the selection chosen.
read more...

Selected Configuration

Model #:

IRU-3435-M

Price:
$767.00 USD
Availability:
Ships 3 - 5 Weeks
Min. Qty:
1 Item

Configuration

reset configuration

Agency Approvals

  • CSA Class 1, Div.2, Groups A, B, C, D

Principle of Operation

  • Continuous Level Sensor

Operating Temperature - Electronics

  • -40° to 60° C (-40° to 140° F)

Accuracy

  • ±0.25% of Span

Resolution

  • 0.1" (2.5 mm)

Response Time

  • Programmable (20 Milliseconds minimum)

Sensing Range

  • 1.25 to 50 feet (0.4 to 15.2 meters)
  • Feet: 0 to 10
  • Feet: 10 to 25
  • Feet: 25 to 35
  • Feet: 35 to 50
  • Meters: 0 to 3.05
  • Meters: 10.66 to 15.24
  • Meters: 3.05 to 7.62
  • Meters: 7.62 to 10.66

Process Connection - Threaded

  • 3" Male NPT

Environmental Protection

  • IP65

Input Power

  • 12-28 Vdc

Frequency

  • 43 kHz

Electrical Connectors

  • 6-Conductor Shielded Cable

Output

  • Isolated 4-20 mA with (2) NPN Trip Points

Enclosure/Body Material

  • PC/PET Blend Transducer
  • PC/PET Upper Housing

Wetted Materials

  • PC/PET Blend

Sensor/Probe Style

  • Ultrasonic

Options

  • Interface with RST-3001 Programmer
  • User Selected Units of Measure