Span Error for Ranges 2, 3, 4, 5 and 6: Correctable to ±0.2% of Reading per psi: 1,000 (bar: 68.95, kPa: 6,895)
Zero Error for Ranges 2, 3, 4, 5 and 6: ±0.033% of URL per psi: 1,000 (bar: 68.95, kPa: 6,895)
Operating Temperature - Display
-20° to 80° C (-4° to 176° F)
-40° to 85° C (-40° to 185° F), Without Damage
Storage Temperature
-40° to 100° C (-40° to 212° F)
Temperature Effect
±[0.02% URL + 0.06% of Span] per 20° C (36° F)
Ambient Temperature
-40° to 85° C (-40° to 185° F)
Humidity
0 to 100% Relative Humidity
Process Temperature
-40° to 100° C (-40° to 212° F)
Accuracy
For Ranges 1, 2, 3, 4, 5, or 6 and 316L Stainless Steel or Hastelloy diaphragm with silicon or haloCarbon filling fluid: 0.1 URL ≤ Span ≤ URL: ± 0.075% or Span. 0.025 URL ≤ Span < 0.1 URL: ± (0.0375+0.00375.URL/Span)% of Span. 0.0083 URL ≤ Span < 0.025 URL: ± (0.0015+0.00465.URL/Span)% of Span.
Span and Zero Adjustments
Non-interactive, via Digital Communication or Local Adjustment
Stability
Ranges 2, 3, 4, 5, and 6: ±0.15% of URL for 5 years at 20° C (68° F) TemperatureCchange and Up to 7 MPA (1,000 psi) of Static Pressure
Volumetric Displacement
>0.15 cm³ (0.01 in³)
Electromagnetic Interference Effect
Approved according to IEC61326-1:2006, IEC61326-2-3:2006, IEC61000-6-4:2006, IEC61000-6-2:2005
Process Connection - Threaded
1/4" NPT
1/2" NPT (With Adapter)
Media
Gas
Liquids and Gases
Steam
Drain/Vent Position
Down
Top
Power Supply Effect
±0.005% of Calibrated Span Per Volt
Input Power
9-32 Vdc
Electrical Connectors
1/2" NPT
Output
Foundation Fieldbus: Digital Only. Complies with IEC 61158-2:2000 (H1): 31.25 kBits/s Voltage Mode, Bus Powered
Turn-On Time
Foundation Fieldbus: Performs within Specifications in Less Than 10 Seconds After Power is Applied to the Transmitter
Display
4-1/2-Digit Numerical and 5-Character Alphanumerical LCD Indicator
Configuration
Foundation Fieldbus: Basic configuration may be done using the local Adjustment magnetic tool if device is fitted with display. Complete configuration is possible using configuration tools.
Control Functions Characteristics
Foundation Fieldbus: Resource (RS), Transducer (TRD), Diagnostics Transducer Block (DIAG), Analog Input (AI), PID Control (PID), Advanced PID Control (APID), Arithmetic (ARTH), Integrator (INTG), Input Selector (ISEL), Signal Characterizer (CHAR), Analog Alarm (AALM), Timer & Logic (TIME), Lead Lag (LLAG), Output Signal Selector & Dynamic Limiter (OSDL), Constant (CT) & Density (DENS).