Images are representations only.

Model iT300 4-20 mA Configurable Vibration Transmitter Module

Brand: Wilcoxon Sensing Technologies
The iT300 transmitter provides an easy means to connect a standard IEPE vibration sensor to a PLC, DCS or SCADA system. The transmitter’s input provides power to and measures the signal from either an accelerometer, piezovelocity sensor or dual output sensor. The input circuitry has a wide frequency response, capable of measuring signals between 0.2 Hz and 20,000 Hz.

The transmitter has two independent processing bands with flexible mapping options to two separate 4-20 mA Analog outputs. The processing channels contain selectable integration, allowing input from accelerometers to be output as acceleration or velocity. Selectable band filters and detector types (i.e. RMS, peak) make it easy to tailor the processing to specific machines or applications.
Features
  • Accepts input from accelerometers (single and dual output) or piezovelocity sensors
  • Input signal is split into two independent processing bands
  • Measures real time sensor bands, BOV, true peak and temperature (if available)
  • Built-in web server allows custom configuration of bandwidth and detection type
  • 2 x 4-20 mA outputs, user-defined
  • Text field for user entry of machine information
  • Configurations can be stored for easy recall
  • Selectable speed range to monitor high- or low- speed machinery
show more
The iT300 transmitter provides an easy means to connect a standard IEPE vibration sensor to a PLC, DCS or SCADA system. The transmitter’s input provides power to and measures the signal from either an accelerometer, piezovelocity sensor or dual output sensor. The input circuitry has a wide frequency response, capable of measuring signals between 0.2 Hz and 20,000 Hz.

The transmitter has two independent processing bands with flexible mapping options to two separate 4-20 mA Analog outputs. The processing channels contain selectable integration, allowing input from accelerometers to be output as acceleration or velocity. Selectable band filters and detector types (i.e. RMS, peak) make it easy to tailor the processing to specific machines or applications.
Features
  • Accepts input from accelerometers (single and dual output) or piezovelocity sensors
  • Input signal is split into two independent processing bands
  • Measures real time sensor bands, BOV, true peak and temperature (if available)
  • Built-in web server allows custom configuration of bandwidth and detection type
  • 2 x 4-20 mA outputs, user-defined
  • Text field for user entry of machine information
  • Configurations can be stored for easy recall
  • Selectable speed range to monitor high- or low- speed machinery

Specifications

Accuracy

  • ± 0.2 % of Full Scale, 100 Hz

Approvals & Certifications

  • CE

Electrical Connectors

  • 14 to 24 AWG
  • Screw Terminal

Frequency

  • Frequency Response, Fmax Options: 200 Hz to 20 kHz
  • Frequency Response: 0.2 to 20 kHz (-3 dB, -0.1 dB)

Input

  • Full Scale Input Range: ± 10 Vdc

Isolation

  • 500 Vac

Loop Resistance

  • Maximum 500 Ω

Mounting

  • 35 mm DIN Rail

Power

  • 11-32 Vdc
  • 3.8 W, Max.
  • IEPE Power Source: 24 Vdc
  • IEPE Power Source: 4.5 mA

Range

  • Dynamic Range: > 90 dB
  • Output Range (Acceleration): 1 to 50 G (10 to 500 m/sec²)
  • Output Range (Displacement): 10 to 200 Mils (0.2 to 5.0 mm)
  • Output Range (Velocity): 0.1 to 5 Ips (2 to 100 mm/sec)

Sensitivity

  • Sensitivity Range (Acceleration): 9 to 11,000 mV/g
  • Sensitivity Range (Velocity): 9 to 11,000 mV/ips

Sensor Input

  • Temperature Sensor Input: 10 mV/°C