Model T9000 Electro-Pneumatic Pressure Controller
FAIRCHILD T9000 I/P Transducer, 4-20 mA, 0-150 psi, 1/2", Feedback, Electrical Connector on RH Side
Price
Request a Quote
Stock
4 In Stock
Description
The Rotork Fairchild T9000 Series Electro-Pneumatic Pressure Controller has a closed-loop, integrated, microprocessor control system that regulates outlet pressure.
The Model T9000 controls pressure in proportion to an analog electrical input signal. An internal feedback sensor monitors output pressure to achieve high accuracy.
You can control the output from the Model T9000 using the keypad or from an analog control signal. You can control the output from the Model T9000D using the keypad and through DeviceNet™ Communication network.
With its integral booster sections, the T9000 series of I/P pressure controllers delivers high accuracy at flow capacities of 1 SCFM in the T9000, 90 SCFM in the T9020, 110 SCFM in the T9040, 220 SCFM in the T9060, and 700 SCFM in the T9080.
Features- High Flow Capacity of up to 700 SCFM (1,190 m3/Hr)
- Output pressure displays in psig, BAR, kPa, or user-defined pressure units
- Reverse acting capability for analog input and output signals
- Select Current or Voltage mode for input signal
- Independently adjustable PID tuning coefficients
- Fully functional keypad and display
- Backlit Liquid Crystal display screen
Specifications
Specifications
Accuracy
- < 0.50 % Output Span
Air Consumption
- 0 at Steady State Output with Deadband at 1 % of Full Scale
Approvals & Certifications
- EMC 89/336/EEC, EMC Directive
BSP Connection
- 1” BSPP Female
- 1” BSPT Female
- 1/2” BSPP Female
- 1/2” BSPT Female
- 1/4” BSPP Female
- 1/4” BSPT Female
- 3/4” BSPP Female
- 3/4” BSPT Female
- 3/8” BSPP Female
- 3/8” BSPT Female
Deadband
- Adjustable from 0 to 10 % of Full Scale
Elastomers
- Fluorocarbon
- Nitrile
Enclosure Finish
- Epoxy Coated
Enclosure, Body Material
- Chromate Treated Aluminum
- Polymer
Exhaust Capacity - Relieving Units Only
- 1 to 350 scfm where Downstream Pressure is psig: 60 (kPa: 400, bar: 4)
Exhaust Port
- Tapped Exhaust Port
Flow Rate
- 1 to 700 scfm at psig: 150 (kPa: 1,034, bar: 10) Supply
Frequency
- -3 dB at 1 Hz Per ISA S26.4.3.1 Load Configuration A
Input
- 0-10 Vdc / 400 ohms Min.
- 4-20 mA / 500 ohms, Max.
- DeviceNet
Input Power
- Power Consumption: < 5 Watts
NPT Connection
- 1” NPT Female
- 1/2” NPT Female
- 1/4” NPT Female
- 3/4” NPT Female
- 3/8” NPT Female
Output
- Analog Output Signal / Impedence: 0-10 Vdc / 400 ohms Min.
- Analog Output Signal / Impedence: 4-20 mA / 500 ohms, Max.
Pressure Range
- bar: 0 to 10
- kPa: 0 to 1,000
- psig: 0 to 150
Pressure Type
- Gauge
RFI/EMI Effect
- < 0.5 % EMC Directive 89/336/EEC European Norms EN 50081-2 & EN 50082-2
Supply Pressure - Maximum
- psig: 200 (kPa: 1,400, bar: 14)
Supply Voltage
- 24 Vdc ± 10 %
Temperature Range
- -18° to 71° C (0° to 160° F)
Trim Material
- Zinc-Plated Steel
Vibration Effect
- < 1 % of Span Under the Following Conditions: 5 to 15 Hz at 0.8” Constant Displacement 15 to 500 Hz at 10 G's
Documentation
Documentation
Installation Instructions
- Installation - Fairchild T9000 PDF 395 KB
- Installation - Fairchild T9000 Analog Output PDF 211 KB
- Installation - Fairchild T9000 Basic Unit PDF 222 KB
- Installation - Fairchild T9010 PDF 454 KB
- Installation - Fairchild T9020 PDF 595 KB
- Installation - Fairchild T9040 PDF 402 KB
- Installation - Fairchild T9060 PDF 431 KB