Images are representations only.

Vegamet 391 Signal Conditioning & Display

Brand: VEGA
The VEGAMET 391 signal conditioning instrument powers the connected 4 to 20 mA/HART sensor, processes and displays the measured values.

The VEGAMET 391 is ideal for simple control tasks in level, gauge and process pressure measurement as well as inventory management (VMI) and remote enquiry.

Comprehensive adjustment functions allow individual adaptations to the respective application.

In water/wastewater management, the instrument stands out with special functions such as pump switching, flow volume measurement, tendency functions and totalizer.
Features
  • Equal Use of all Pumps Through Integrated Pump Management
  • Completely Integrated Functional Unit for Flow Volume Measurement
  • Simple Integration into the Intranet/Extranet via Integrated Web Server
show more
The VEGAMET 391 signal conditioning instrument powers the connected 4 to 20 mA/HART sensor, processes and displays the measured values.

The VEGAMET 391 is ideal for simple control tasks in level, gauge and process pressure measurement as well as inventory management (VMI) and remote enquiry.

Comprehensive adjustment functions allow individual adaptations to the respective application.

In water/wastewater management, the instrument stands out with special functions such as pump switching, flow volume measurement, tendency functions and totalizer.
Features
  • Equal Use of all Pumps Through Integrated Pump Management
  • Completely Integrated Functional Unit for Flow Volume Measurement
  • Simple Integration into the Intranet/Extranet via Integrated Web Server

Specifications

Brand

Accuracy

  • 0.1 % of 20 mA (± 20 µA)

Ambient Temperature Range

  • -20° to 60° C (-4° to 140° F)

Applications

  • Gauge
  • Level
  • Measured Value Indication & Simple Control Functions
  • Process Pressure

Approvals & Certifications

  • ATEX
  • CSA
  • FM
  • IEC
  • SIL 2

Communication

  • 10/100 MegaBits - Data Transmission
  • Digital for HART Sensors
  • HART Protocol

Consumption

  • 3 W - Max.
  • 7 VA - Max.

Display

  • LCD Display - 65 x 32 mm, Digital & QuasiAnalog Display

Electrical Connectors

  • 14 AWG, (2.5 mm²) - Max.
  • Pluggable Spring-Loaded Terminal with Coding

Environmental Protection

  • IP20
  • IP65

Hysteresis

  • Adjustable

Indication

  • Green LED - Status, Operating Voltage
  • Red LED - Status, Fault Signal
  • Yellow LED x 6 - Status Operating Relay 1 to 6

Input

  • 4-20 mA (HART)
  • Active Sensor - Sensor Supply through Vegamet 391
  • Passive Sensor - Sensor Has an Own Power Supply

Interface Connection

  • Plug Connection - Mini-B (4-Pole) USB Interface
  • RS-232 - 1 X, cannot be combined with Ethernet
  • RS-232 - 1 X, cannot be combined with RS-232: Ethernet Interface (Optional)
  • USB Port - 2.0 (Fullspeed)

Loop Resistance

  • 500 ohms, Max.

Mounting

  • Carrier Rail 35 x 7.5 According to EN 50022
  • Front Panel Mounting
  • Wall Mounted

Operating Voltages

  • 20-253 Vac
  • 20-253 Vdc
  • 50/60 Hz

Output

  • 0 to 20 mA - Current Output
  • 4-20 mA - Current Output

Relay Output

  • Breaking Capacity: 50 mW Min., 500 VA, 54 W DC, Max.
  • Quantity: 6 x Operating Relay
  • Switching Current: 10 µA Min., 3 A AC, 1 A DC, Max.
  • Switching Voltage: 10 mVdc Min., 250 Vac, 60 Vdc, Max.

Sensor Input

  • Active Input: Sensor Supply through Vegamet 391
  • Number of Sensors 1 x 4-20 mA (HART)
  • Passive Input: Sensor Has an Own Power Supply