Description
The Rotork Fairchild T5420 is a Digital-Pneumatic Transducer, compatible with most digital systems using TTL and CMOS Logic.
Its Fail Safe High or Low will return the field reversible output to 3 psig for Direct Acting Mode or to 15 psig for Reverse Acting Mode if the power is lost, regardless of the logic selected.
The Integral Volume Booster Output of the T5420 provides a flow capacity of 45 SCFM (76.5 m3/Hr), to meet input requirements of final control elements requiring a higher capability output signal, increased output pressure, and/or increased flows.
Features- Uses common 8 bit data instructions
- Fail safe High or Low
- Field Reversible Feature
- Integrated Volume Booster Output
- Vibration resistance
- Various Mounting Configurations
- External Zero Adjustment
Configure
Specifications
Specifications
Air Consumption
- 0.16 scfm (0.27 m³/hour) - Max.
Ambient Temperature Range
- 0° to 65.5° C (32° to 150° F)
Ball Material
- Brass
- Sapphire
Conduit Connection
- 1/2” NPT
Enclosure, Body Material
- Aluminum
Flow Capacity
- 15 scfm (25.5 m³/hour) - Max.
- 45 scfm (76.5 m³/hour) at psig: 100 (kPa: 700, bar: 7)
Hysteresis
- Within 0.1 % of Full Scale
Independent Linearity
- + 0.25 % of Full Scale
Mounting
- Bracket Kit
NPT Inlet
- 1/4” NPT Female
NPT Outlet
- 1/4” NPT Female
Orifice Material
- Brass
- Sapphire
Power
- 115 Vdc - 3 Watts
- 230 Vdc - 3 Watts
- 24 Vdc - 3 Watts
Pressure Range
- bar: 0.2 to 6.2
- kPa: 20 to 620
- psig: 3 to 90
Pressure Type
- Gauge
Ratio
- 1:1
- 1:2
- 1:3
- 1:4
- 1:5
- 1:6
Repeatability
- Within 0.1 % of Full Scale
Resolution
- 0.4 % of Span
Supply Pressure
- psig: 20 + 2 (kPa: 150 + 15, bar: 1.5 + 0.15)
Supply Pressure Effect
- 1 % of Span for psig: 2 (kPa: 14, bar: 0.14) Supply Change