Images are representations only.

NivoGuide® - NG 3100 Radar Sensors

Brand: UWT GmbH
Application Area

The guided radar sensor NivoGuide® NG 3100 is used for continuous level measurement in bulk solids applications from a Dk value of 1.5.

The large measuring range up to a vessel height of 75 m covers many applications in bulk solids.

Intuitive operation and a Quick Start Wizard makes commissioning simple and safe.
Features
  • Simple, menu-driven commissioning and diagnostics with operating module and display
  • Maintenance-free sensor
  • Use in narrow vessels possible due to guided radar signal
show more
Application Area

The guided radar sensor NivoGuide® NG 3100 is used for continuous level measurement in bulk solids applications from a Dk value of 1.5.

The large measuring range up to a vessel height of 75 m covers many applications in bulk solids.

Intuitive operation and a Quick Start Wizard makes commissioning simple and safe.
Features
  • Simple, menu-driven commissioning and diagnostics with operating module and display
  • Maintenance-free sensor
  • Use in narrow vessels possible due to guided radar signal

Specifications

Brand

Measurement Pprinciple

  • Guided Radar (TDR)

Measuring Task

  • Continuous Level Measurement

Version

  • Rod Version
  • Rope Version
  • Coated Rope Version

Medium

  • Solids

Mounting Position

  • Top
  • In a Standpipe
  • In a Bypass
  • On a Socket

Ambient Temperature

  • -40°C … +80°C (-40 … +176°F)

Process Temperature

  • -40°C … +200°C (-40 … +392°F)

Process Pressure

  • -1 bar … +40 bar (-14.5 psi … +580 psi)

Minimum Sensitivity

  • DK ≥ 1.6

Housing Type

  • Flameproof
  • Flameproof Double Chamber

Housing Material

  • Aluminium
  • Stainless Steel 1.4404 (316L)

Housing Protection Rating

  • IP68, Type 6P

Threaded Connection

  • ≥ G ¾"
  • ≥ NPT ¾"

Flange Connection

  • ≥ DN50 / ≥ 1½"

Hygienic Fittings

  • Triclamp Adapter

Wetted Materials

  • Stainless Steel 1.4404 (316L)
  • PA
  • Stainless Steel 1.4401 (316)
  • FKM
  • FFKM
  • EPDM
  • PPS
  • PEEK

Mechanical Load

  • Rod (Ø 16 mm): 30 Nm
  • PA-Rope (Ø 6 mm): 8 kN
  • Rope (Ø 4 mm): 12 kN
  • Rope (Ø 6 mm): 30 kN
  • PA-Rope (Ø 11 mm): 30 kN

Accuracy

  • ±2 mm (±0.07")

Minimum Immersion Length

  • Rod: 300 mm (11.8")
  • Coated Rope: 500 mm (19.7")
  • Rope: 500 mm (19.7")

Maximum Immersion Length

  • Coated Rope: 65 m (213.3')
  • Rope: 75 m (246')
  • Rod: 6 m (19.82')

Power Supply

  • 9.6...35 VDC

Signal Output

  • 4...20 mA/ HART (2-wire)

Approvals

  • CE, General purpose, ATEX, IEC-Ex, INMETRO, TR-CU, FM

Explosion Protection

  • Dust Ignition-proof (Ex t)
  • Intrinsic Safe (Ex i)
  • Explosion Proof/ Flame Proof (Ex d)
  • Non-Incendive

SIL Qualification

  • SIL 2/3

User Interface

  • LCD Display with Push Buttons
  • PACTware (DTM)
  • HART Modem

Optical Indicator

  • Display

Adjustment Possibility

  • Self Diagnostics
  • Menu-Driven Quick Start
  • Echo Analysis
  • Volume Table

Applications

  • Animal Feed
  • Chemicals
  • Power
  • Metal
  • Building, Cement & Quarry
  • Food & Beverage
  • Wood

Documentation

Certificates