Description
The A4 Outlet Pressure Regulator modulates flow of refrigerant gas or liquid to maintain a constant downstream pressure as set-for, despite fluctuations in load.
The regulator will gradually close when downstream pressure begins to rise above the setting and will gradually open when pressure begins to fall below the setting.
These valves are generally ordered with close coupled strainer to prevent entrance of foreign material into the valve and the rest of the system.
Features
- Pilot operated characterized Modulating Plug precise control
- Suitable for all common refrigerants and oil
- 27.6 bar (400 psig) design pressure (MRP)
- Flanges for threaded or welded steel pipe and copper tube (copper not for ammonia)
- Interchangeable parts
- Easy to service
- Close coupled strainers, optional
- Many control variations are possible with the use of a few Modules and kits
- Stainless Steel Diaphragm
- Chrome Plated Pilot Seat
- Manual Opening Stem
Specifications
Specifications
Brand
Body Material
- Gray Iron
Capacity Plug
- Full Capacity
Check Valve Type
- None
Coil Type
- 120 AC~ 60 Hz- Leaded Green LED Pilot Light, No Coil AC- No Coil Style, 120 AC~ 60 Hz- Leaded Standard
Connection Size
- None, 2-1/2", 2"
Flange Type
- None or Socket Weld
Flow Coefficient (Cv)
- 7.2 to 70 Cv
Flow Coefficient (Kv)
- 29 to 42 Kv
High Pressure Set Point (bar)
- 15 psig or 40 psig
High Pressure Set Point (psig)
- 1.0 bar or 2.8 bar
Low Pressure Set Point (bar)
- 1.0 bar
Low Pressure Set Point (psig)
- 15 psig
Maximum Rated Pressure (bar)
- 27.6 bar or 20.7 bar
Maximum Rated Pressure (psig)
- 400 or 300 psig
Maximum Working Temperature (°C)
- 105°
Maximum Working Temperature (°F)
- 220° F
Minimum Working Temperature (°C)
- -45° C
Minimum Working Temperature (°F)
- -50° F
Model Number
- Please Configure Part for Model Number
Motor Type
- None, Motor Assembly- 120 V 50/60 Hz 4-20 mA Standard CAM, Mounting Kit- Standard CAM
Plating
- No Plating
Port Size (inch)
- 3/4" to 2-1/2"
Port Size (mm)
- 20 mm to 65 mm
Pressure Range (bar)
- 500 mmHg to 8.3 bar to 500 mmHg to 8.3 bar, 500 mmHg to 8.3 bar to 0.35 to 10 bar, 0.35 to 10 bar to 0.35 to 10 bar
Pressure Range (psig)
- 20 Hg to 120 psig to 20 Hg to 120 psig, 20 Hg to 120 psig to 5 to 150 psig, 5 to 150 psig to 5 to 150 psig
Pressure Regulator Type
- Dual Outlet- Externally Equalized (Both Pilots), Dual Outlet- Externally Equalized (Low Pilot Only), Dual Outlet- Electric Shut-Off, Dual Outlet- Electrically Compensated
Strainer Type
- Without Strainer or with Strainer
Valve Material
- Standard Valve Material
Valve Type
- A4ADOE, A4AODE, A4AODS, A4AODM
Applications
Applications
- Protect Compressor Motor from Overload (Hold-back
- Hot Gas Bypass Capacity Control
- Limit Refrigerant Pressure in a Liquid Line
- Prevent Deep Vacuum in Booster Suction
- Prevent Pressure Rise in Suction Main
- Hot Gas Defrost Control