Features:
  • Locks in "Last Position" to accurately capture setpoint
  • Extrernely low drift after power loss permits transducer to maintain set point
  • IP65 Rating to handle moist applications
  • Single part number makes it easy to specify and cover all your needs
  • Superior Construction including a moisture resistant PCB and Zinc coated components
Failure Mode:
  • Output Pressure locks at last value when signal fails
Drift Rate:
  • 2% per hour Maximum
The above description encapsulates the entire product series. Specifications for individual configurations may vary depending on the selection chosen.
read more...

Selected Configuration

Model #:

Model T6100

Price:
Request a Quote
Availability:
Out of Stock
Min. Qty:
1 Item

Configuration

reset configuration

Agency Approvals

  • EMC 89/336/EEC
  • European Norms EN 50081-2 and EN 50082-2
  • IEC Standard 801-3 1984

Environmental Protection

  • IP65

Pressure Range

  • bar: 0.2 to 1
  • kPa: 20 to 100
  • psig: 3 to 15

Supply Pressure

  • psig: 20 to 40 (kPa: 150 to 280, bar: 1.5 to 2.8)

Supply Pressure Effect

  • psig: 20 to 40 (bar: 1.5 to 2.8, kPa: 150 to 280)

Pressure Type

  • Gauge

Temperature Range

  • -30° to 65° C (-20° to 150° F)

Independent Linearity

  • +0.5% Full Scale

Hysteresis

  • 0.25% Full Scale

Air Consumption

  • 5.0 SCFH (0.14 m³/hr)

Repeatability

  • 0.25% Full Scale

RFI/EMI Effect

  • <0.5% of Span at 30 V/m class 3 Band ABC (20-1,000 mHz) per SAMA PMC 33.1 1978 and <0.5% of Span at 10 V/m level 3, 27-500 mHz band per IEC Standard 801-3 1984. EMC Directive 89/336 EEC European Norms EN 50081-2 and EN 50082-2

Process Connection - Threaded

  • 1/4" Female NPT
  • 1/2" Female NPT
  • 1/2" Female BSPT

Input

  • 4-20 mA (two wire, 7 Volts Drop Maximum at 20 mA)

Flow Rate

  • 5 SCFM (8.5 m³/hr) at psig: 21 (bar: 1.7, kPa: 170) Supply psig: 9 (bar: 0.6, kPa: 60) Output

Electrical Connectors

  • 1/2" NPT Conduit
  • 33 mm DIN 43650 Connector Mountable in Four Directions
  • Junction Box

Mounting

  • Surface Mounting, or 2" Pipe Mount brackets Available

Mounting Position

  • Vertical Preferred; Other Positions Re-zero

Enclosure/Body Material

  • Aluminum

Diaphragm Material

  • Nitrile

Orifice Material

  • Nickel-Plated Brass

Trim Material

  • Zinc-Plated Steel