The 604TU Series is a general purpose temperature switch with a stainless steel capillary tube and armored jacket probe port fitting.

It is constructed with an integral terminal box and switch design and easy set point adjustment.

It is also easily mounted to bulkheads and UL certified with NEMA 4 and IP65 rating. It has high vibration and shock resistance utilizing Dual Snap® disc spring technology.

Features

  • Adjustable Set Point Range
    • Increasing
      • -30° to 630° F
      • -34° to 332° C
    • Decreasing
      • -39° to 624° F
      • -39° to 329° C
  • Deadband - Approximate
    • At Bottom of Range: 9° to 24° F, 5° to 13° C
    • At Top of Range: 3° to 6° F, 2° to 8° C
  • Probe Temperature - Maximum: 200° to 650° F, 93° to 343° C
  • Wetted Materials
    • Temperature Probe: 300 Stainless Steel & Graphite
    • Capillary Tube: Lubricated Glass Fiber
  • Relay: SPDT or DPDT
  • UL, CE Mark, General Purpose
The 604TU Series is a general purpose temperature switch with a stainless steel capillary tube and armored jacket probe port fitting.

It is constructed with an integral terminal box and switch design and easy set point adjustment.

It is also easily mounted to bulkheads and UL certified with NEMA 4 and IP65 rating. It has high vibration and shock resistance utilizing Dual Snap® disc spring technology.

Features

  • Adjustable Set Point Range
    • Increasing
      • -30° to 630° F
      • -34° to 332° C
    • Decreasing
      • -39° to 624° F
      • -39° to 329° C
  • Deadband - Approximate
    • At Bottom of Range: 9° to 24° F, 5° to 13° C
    • At Top of Range: 3° to 6° F, 2° to 8° C
  • Probe Temperature - Maximum: 200° to 650° F, 93° to 343° C
  • Wetted Materials
    • Temperature Probe: 300 Stainless Steel & Graphite
    • Capillary Tube: Lubricated Glass Fiber
  • Relay: SPDT or DPDT
  • UL, CE Mark, General Purpose
Models matching criteria: 19
CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, DPDT view more
  • Adjustable Set Point Range:
    • Increasing: +35°F to +140°F, +2°C to +60°C
    • Decreasing: +21°F to +135°F, -6°C to +57°C
    • Deadband: Approximately
      • At Bottom of Range: 14°F, 4°C
      • At Top of Range: 5°F, 3°C
    • Probe Temperature (Maximum): +300°F, +149°C
    • Wetted Materials:
      • Temperature Probe: 300 Stainless Steel & Graphite
      • Capillary Tube: Lubricated Glass Fiber
      • Relay: DPDT
    • UL, CE Mark, NACE, General Purpose
    5 - 7 weeks
    $1,316.11 USD
    Does not ship to TN, United States
    Non-Cancellable / Non-Refundable
    CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, DPDT view more
    • Adjustable Set Point Range:
      • Increasing: +90°F to +210°F, +32°C to +99°C
      • Decreasing: +75°F to +205°F, +24°C to +96°C
    • Deadband: Approximately
      • At Bottom of Range: 15°F, 8°C
      • At Top of Range: 5°F, 3°C
    • Probe Temperature (Maximum): +300°F, +149°C
    • Wetted Materials:
      • Temperature Probe: 300 Stainless Steel & Graphite
      • Capillary Tube: Lubricated Glass Fiber
      • Relay: DPDT
    • UL, CE Mark, NACE, General Purpose
    5 - 6 weeks
    $1,316.11 USD
    Does not ship to TN, United States
    Non-Cancellable / Non-Refundable
    CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary view more
    • Adjustable Set Point Range:
      • Increasing: +35°F to +140°F, +2°C to +60°C
      • Decreasing: +21°F to +135°F, -6°C to +57°C
      • Deadband: Approximately
        • At Bottom of Range: 14°F, 4°C
        • At Top of Range: 5°F, 3°C
      • Probe Temperature (Maximum): +300°F, 149°C
      • Wetted Materials:
        • Temperature Probe: 300 Stainless Steel & Graphite
        • Capillary Tube: Lubricated Glass Fiber
      • Relay: SPDT
      • UL, CE Mark, NACE, General Purpose
      5 - 7 weeks
      $2,480.21 USD
      Does not ship to TN, United States
      CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 15` Capillary view more
      • Adjustable Set Point Range:
        • Increasing: +35°F to +140°F, +2°C to +60°C
        • Decreasing: +21°F to +135°F, -6°C to +57°C
      • Deadband: Approximately
        • At Bottom of Range: 14°F, 4°C
        • At Top of Range: 5°F, 3°C
      • Probe Temperature (Maximum): +300°F, +149°C
      • Wetted Materials:
        • Temperature Probe: 300 Stainless Steel & Graphite
        • Capillary Tube: Lubricated Glass Fiber
      • Relay: SPDT
      • Contacts: Gold
      • UL, CE Mark, NACE, General Purpose
      13 - 14 weeks
      $2,606.89 USD
      Does not ship to TN, United States
      CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 25` Capillary view more
      • Adjustable Set Point Range:
        • Increasing: +90°F to +210°F, +32°C to +99°C
        • Decreasing: +75°F to +195°F, +27°C to +91°C
      • Deadband: Approximately
        • At Bottom of Range: 15°F, 5°C
        • At Top of Range: 5°F, 8°C
      • Probe Temperature (Maximum): +300°F, +149°C
      • Wetted Materials:
        • Temperature Probe: 300 Stainless Steel & Graphite
        • Capillary Tube: Lubricated Glass Fiber
      • Relay: SPDT
      • UL, CE Mark, NACE, General Purpose
      13 - 14 weeks
      $2,671.64 USD
      Does not ship to TN, United States
      CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary view more
      • Adjustable Set Point Range:
        • Increasing: -30°F to +55°F, -34°C to +13°C
        • Decreasing: -39°F to +52°F, -39°C to +11°C
      • Deadband: Approximately
        • At Bottom of Range: 9°F, 5°C
        • At Top of Range: 3°F, 2°C
      • Probe Temperature (Maximum): +200°F, +121°C
      • Wetted Materials:
        • Temperature Probe: 300 Stainless Steel & Graphite
        • Capillary Tube: Lubricated Glass Fiber
      • Relay: SPDT
      • UL, CE Mark, NACE, General Purpose
      Does not ship to TN, United States
      Contact For Inventory
      CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, Gold Contacts view more
      • Adjustable Set Point Range:
        • Increasing: +35°F to +140°F, +2°C to +60°C
        • Decreasing: +21°F to +135°F, -6°C to +57°C
      • Deadband: Approximately
        • At Bottom of Range: 14°F, 4°C
        • At Top of Range: 5°F, 3°C
      • Probe Temperature (Maximum): +300°F, +149°C
      • Wetted Materials:
        • Temperature Probe: 300 Stainless Steel & Graphite
        • Capillary Tube: Lubricated Glass Fiber
      • Relay: SPDT
      • Contacts: Gold
      • UL, CE Mark, NACE, General Purpose
      Does not ship to TN, United States
      5 - 7 weeks
      CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 10` Capillary, Gold Contacts
      Does not ship to TN, United States
      5 - 7 weeks
      CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary view more
      • Adjustable Set Point Range:
        • Increasing: +175°F to +310°F, +80°C to +154°C
        • Decreasing: +159°F to +305°F, +71°C to +152°C
        • Deadband: Approximately
          • At Bottom of Range: 16°F, 9°C
          • At Top of Range: 5°F, 2°C
        • Probe Temperature (Maximum): +500°F, +260°C
        • Wetted Materials:
          • Temperature Probe: 300 Stainless Steel & Graphite
          • Capillary Tube: Lubricated Glass Fiber
        • Relay: SPDT
        • UL, CE Mark, NACE, General Purpose
        Does not ship to TN, United States
        5 - 7 weeks
        CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 10` Capillary view more
        • Adjustable Set Point Range:
          • Increasing: +175°F to +310°F, +80°C to +154°C
          • Decreasing: +159°F to +305°F, +71°C to +152°C
          • Deadband: Approximately
            • At Bottom of Range: 16°F, 9°C
            • At Top of Range: 5°F, 2°C
          • Probe Temperature (Maximum): +500°F, +260°C
          • Wetted Materials:
            • Temperature Probe: 300 Stainless Steel & Graphite
            • Capillary Tube: 10' Capillary, Lubricated Glass Fiber
          • Relay: SPDT
          • UL, CE Mark, NACE, General Purpose
          Does not ship to TN, United States
          5 - 7 weeks
          CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 15` Capillary view more
          • Adjustable Set Point Range:
            • Increasing: +175°F to +310°F, +80°C to +154°C
            • Decreasing: +159°F to +305°F, +71°C to +152°C
            • Deadband: Approximately
              • At Bottom of Range: 16°F, 9°C
              • At Top of Range: 5°F, 2°C
            • Probe Temperature (Maximum): +500°F, +260°C
            • Wetted Materials:
              • Temperature Probe: 300 Stainless Steel & Graphite
              • Capillary Tube: 15' Capillary, Lubricated Glass Fiber
            • Relay: SPDT
            • UL, CE Mark, NACE, General Purpose
            Does not ship to TN, United States
            5 - 7 weeks
            CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, Gold Contacts view more
            • Adjustable Set Point Range:
              • Increasing: +175°F to +310°F, +80°C to +154°C
              • Decreasing: +159°F to +305°F, +71°C to +152°C
            • Deadband: Approximately
              • At Bottom of Range: 16°F, 9°C
              • At Top of Range: 5°F, 2°C
            • Probe Temperature (Maximum): +500°F, +260°C
            • Wetted Materials:
              • Temperature Probe: 300 Stainless Steel & Graphite
              • Capillary Tube: Lubricated Glass Fiber
            • Relay: SPDT
            • Contacts: Gold
            • UL, CE Mark, NACE, General Purpose
            Does not ship to TN, United States
            5 - 7 weeks
            CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 10` Capillary, Gold Contacts
            Does not ship to TN, United States
            5 - 7 weeks
            CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, Gold Contacts view more
            • Adjustable Set Point Range:
              • Increasing: +275°F to +420°F, +135°C to +216°C
              • Decreasing: +256°F to +414°F, +123°C to +212°C
            • Deadband: Approximately
              • At Bottom of Range: 19°F, 12°C
              • At Top of Range: 6°F, 4°C
            • Probe Temperature (Maximum): +500°F, +260°C
            • Wetted Materials:
              • Temperature Probe: 300 Stainless Steel & Graphite
              • Capillary Tube: Lubricated Glass Fiber
            • Relay: SPDT
            • Contacts: Gold
            • UL, CE Mark, NACE, General Purpose
            Does not ship to TN, United States
            5 - 7 weeks
            CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, DPDT view more
            • Adjustable Set Point Range:
              • Increasing: +175°F to +310°F, +80°C to +154°C
              • Decreasing: +159°F to +305°F, +71°C to +152°C
            • Deadband: Approximately
              • At Bottom of Range: 16°F, 9°C 
              • At Top of Range: 5°F, 2°C
            • Probe Temperature (Maximum): +500°F, +260°C
            • Wetted Materials:
              • Temperature Probe: 300 Stainless Steel & Graphite
              • Capillary Tube: Lubricated Glass Fiber
            • Relay: DPDT
            • UL, CE Mark, NACE, General Purpose
            Does not ship to TN, United States
            5 - 7 weeks
            CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, DPDT view more
            • Adjustable Set Point Range:
              • Increasing: +380°F to +525°F, +193°C to +274°C
              • Decreasing: +355°F to +520°F, +179°C to +271°C
            • Deadband: Approximately
              • At Bottom of Range: 25°F, 4°C 
              • At Top of Range: 5°F, 3°C
            • Probe Temperature (Maximum): +500°F, +260°C
            • Wetted Materials:
              • Temperature Probe: 300 Stainless Steel & Graphite
              • Capillary Tube: Lubricated Glass Fiber
            • Relay: DPDT
            • UL, CE Mark, NACE, General Purpose
            Does not ship to TN, United States
            7 - 9 weeks
            CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 15` Capillary, DPDT view more
            • Adjustable Set Point Range:
              • Increasing: +380°F to +525°F, +193°C to +274°C
              • Decreasing: +355°F to +520°F, +179°C to +271°C
              • Deadband: Approximately
                • At Bottom of Range: 25°F, 4°C
                • At Top of Range: 5°F, 3°C
              • Probe Temperature (Maximum): +600°F, +316°C
              • Wetted Materials:
                • Temperature Probe: 300 Stainless Steel & Graphite
                • Capillary Tube: 15' Capillary, Lubricated Glass Fiber
                • Relay: DPDT
              • UL, CE Mark, NACE, General Purpose
              Does not ship to TN, United States
              5 - 7 weeks
              CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 5` Capillary, DPDT view more
              GENERAL DESCRIPTION STD 604TUM2, FACTORY SET, SPECIAL PROBE (1.875) INCR: 130 DEG F DECR: BY 120 DEG F PROOF: 300 DEG F ELEC RATING: STD
              Does not ship to TN, United States
              5 - 7 weeks
              CCS DUAL-SNAP Temperature Switch, Non-Haz. Area, 1/2" NPT 300 SST, 25` Capillary, DPDT view more
              • Adjustable Set Point Range:
                • Increasing: +175°F to +310°F, +80°C to +154°C
                • Decreasing: +159°F to +305°F, +71°C to +152°C
              • Deadband: Approximately
                • At Bottom of Range: 16°F, 9°C 
                • At Top of Range: 5°F, 2°C
              • Probe Temperature (Maximum): +500°F, +260°C
              • Wetted Materials:
                • Temperature Probe: 300 Stainless Steel & Graphite
                • 25' Capillary Tube: Lubricated Glass Fiber
              • Relay: DPDT
              • UL, CE Mark, NACE, General Purpose
              Does not ship to TN, United States
              5 - 7 weeks

              Specifications

              Area Classification

              • Non-Hazardous Area

              Approvals

              • CE
              • CCC
              • CSA
              • UL

              Adjustable or Pre-Set Set Point

              • Field Adjustable

              Set Point °C  ▲

              • Minimum: -34
              • Maximum: 332

              Set Point °C  ▼

              • Minimum: -39
              • Maximum: 329

              Set Point °F  ▲

              • Minimum: -30
              • Maximum: 630

              Set Point °F  ▼

              • Minimum: -39
              • Maximum: 624

              Deadband, Approx. at Top of Range °C

              • Minimum: 2
              • Maximum: 4

              Deadband, Approx. at Bottom of Range °C

              • Minimum: 4
              • Maximum: 13

              Deadband, Approx. at Top of Range °F

              • Minimum: 3
              • Maximum: 6

              Deadband, Approx. at Bottom of Range °F

              • Minimum: 9
              • Maximum: 25

              Process Connection Type & Size

              • 1/2"-14 NPT Male

              Process Connection Material

              • 300 Stainless Steel

              NACE

              • NACE MR 0175 / ISO 15156

              O-Ring

              • No O-Ring

              Enclosure Rating

              • IP 65
              • IP 66
              • NEMA 4
              • NEMA 4X
              • NEMA 13

              Capillary Length

              • 5 ft
              • 10 ft
              • 15 ft
              • 25 ft

              Max. Probe Temp. °C

              • Minimum: 66
              • Maximum: 343

              Max. Probe Temp. °F

              • Minimum: 150
              • Maximum: 650

              Operating Temp. Range °C

              • Minimum: -40
              • Maximum: 86

              Operating Temp. Range °F

              • Minimum: -40
              • Maximum: 186

              Electrical Connection Size

              • 3/4" NPT Female Conduit Connection

              Electrical Termination Type

              • Terminal Strip

              Electrical Contacts Form

              • SPDT
              • DPDT
              • Double Break

              Electrical Contacts Material

              • Silver
              • Gold

              Voltage Electrical Rating

              • 0 - 250 VAC
              • 251 - 480 VAC
              • 0 - 125 VDC
              • 126 - 250 VDC

              Ampere Rating

              • 0.2 to 15 A

              RoHS

              Housing Material

              • Aluminum

              Gender

              • Male

              NACE & NIST

              • NACE MR-0175: 2003

              Operating Temperature

              • -40° to 86° C (-40° to 187° F)

              Electrical Contacts

              • Silver
              • Gold

              Deadband, Approximate - Bottom of Range

              • -13° to -4° C (9° to 25° F)
              • 4° to 13° C (39° to 55° F)

              Standard Features

              • Internal Case Ground
              • Weatherproof

              Environmental Protection

              • IP 65
              • IP 66
              • NEMA 4
              • NEMA 13

              Process Connection

              • 1/2" NPT Male

              Proof Pressure

              • bar: 103.4
              • kPa: 10,342
              • psig: 1,500

              Maximum Sensor, Probe Temperature

              • 121° to 343° C (250° to 650° F)

              Set Point Range - Increasing

              • -34° to 332° C
              • -34° to 332° C (-29° to 630° F)

              O-Ring Material

              • None

              Electrical Rating

              • 1 A at 125 Vac, 50/60 Hz
              • 15 A at 125/250/480 Vac Resistive, 0.4 A at 125 Vdc, 0.2 A at 250 Vdc
              • 5 A at 125/250 Vac Resistive, 5 A at 28 Vdc, 0.5 A at 125 Vdc

              Switch Type

              • SPDT
              • DPDT

              Capillary Length

              • 10 ft (3 m)
              • 15 ft
              • 25 ft
              • 5 ft (1.524 m)

              Approvals & Certifications

              • CE
              • CRN - Canadian Registration Number
              • CRN - Alberta
              • CRN - British Columbia
              • CRN - Manitoba
              • CRN - N.W. Territories
              • CRN - Saskatchewan
              • CSA
              • cUL
              • EMC
              • LVD
              • PED
              • RoHS
              • UL

              Sensor, Probe Material

              • Stainless Steel & Graphite

              Deadband, Approximate - Top of Range

              • -16° to -14° C (3° to 6° F)
              • 2° to 8° C (36° to 46° F)

              Enclosure, Body Material

              • Aluminum

              Set Point Range - Decreasing

              • -39° to 329° C
              • -39° to 329° C (-38° to 624° F)

              Capillary Material

              • Lubricated Glass Fiber

              System Pressure

              • bar: 86
              • kPa: 8,618
              • psig: 1,250

              Electrical Connectors

              • Terminal Strip - Internal

              Adjustment Type

              • Field Adjustable

              Area Classification

              • Non-Hazardous Area

              Applications

              • Power Generation
              • Rail Car
              • Fluid Management
              • Manufacturing Process
              • Utilities, Water Treatment and Waste
              • Chemical Refining and Processing
              • Heavy Vehicles
              • Safety Systems